Features/SpecificationsPower Supply/Charger:
- 12VDC and/or 24VDC output.
- Output Power Options:
- a) 5.5 amp @ 12VDC plus 5.5 amp @ 12VDC.
- b) 5.7 amp @ 24VDC plus 5.7 amp @ 24VDC.
- c) 5.5 amp @ 12VDC plus 5.7 amp @ 24VDC.
- 115VAC 60Hz, 7.0 amp input.
- Input fuse rated @ 3.5 amp.
- Filtered and electronically regulated outputs.
- Built-in charger for sealed lead acid or gel type batteries.
- Maximum charge current .7 amp.
- Automatic switch over to stand-by battery when AC fails.
- Zero voltage drop when unit switches over to battery backup (AC failure condition).
- Short circuit and thermal onerload protection with auto reset.
- AC input and DC output LED indicators.
- AC fail supervision (form "C" contact).
- Battery fail and battery presence supervision (form "C" contact).
Access Power Controller:
- Sixteen (16) Access Control System trigger inputs.
- Input options:
- a) Sixteen (16) normally open (NO) inputs.
- b) Sixteen (16) open collector inputs.
- c) Any combination of the above.
- Sixteen (16) independently controlled PTC protected outputs.
- Output options:
- a) Sixteen (16) Fail-Safe and/or Fail-Secure power outputs.
- b) Sixteen (16) form “C” 5 amp rated relay outputs.
- c) Any combination of the above.
- Sixteen (16) auxiliary power outputs (unswitched) (outputs are rated 3.5 amp).
- Power supply input options:
- a) One (1) common power input for either ACM8 and lock power (factory installed).
- b) Two (2) isolated power inputs (external power supply is required).
- (current is determined by the power supply connected, not to exceed a maximum of 10 amp total).
- ACM8 board's main fuse is rated @ 10 amp.
- Red LEDs indicate outputs are triggered (relays energized).
- Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the Sixteen (16) outputs.
- Fire Alarm disconnect input options:
- a) Normally open (NO) or normally closed (NC) dry contact input.
- b) Polarity reversal input from FACP signaling circuit.
- Alarm output relay indicates that FACP input is triggered (form “C” contact rated @ 1 amp 28VDC not evaluated by UL).
- Green LED indicates FACP disconnect is triggered.
- Lifetime Warranty.
Enclosure- Accommodates up to four (4) 12VDC/12AH batteries.
- Dimensions: 26”H x 19”W x 6.25”D.
- 1/2" and 3/4" combination knockouts.
Similar Altronix ProductsMAXIM33 Power Supply 1: 5.5 amp @ 12VDC or 5.7 amp @ 24VDC, 8 fused protected Fail Safe/Fail Secure outputs. Power Supply 2: 5.5 amp @ 12VDC or 5.7 amp @ 24VDC, 8 fused protected Fail Safe/Fail Secure outputs. MAXIM3D 5 amp @ 12VDC or 5.4 amp @ 24VDC, 16 PTC protected Fail Safe/Fail Secure outputs. MAXIM5D 9 amp @ 12VDC, 16 PTC protected Fail Safe/Fail Secure outputs. MAXIM7D 9.4 amp @ 24VDC, 16 PTC protected Fail Safe/Fail Secure outputs. MAXIM11D Power Supply 1: 3.5 amp @ 12VDC or 2.7 amp @ 24VDC, 8 PTC protected Fail Safe/Fail Secure outputs. Power Supply 2: 3.5 amp @ 12VDC or 2.7 amp @ 24VDC, 8 PTC protected Fail Safe/Fail Secure outputs. MAXIM55D Power Supply 1: 9.5 amp @ 12VDC, 8 PTC protected Fail Safe/Fail Secure outputs. Power Supply 2: 9.5 amp @ 12VDC, 8 PTC protected Fail Safe/Fail Secure outputs. MAXIM75D Power Supply 1: 9.7 amp @ 24VDC, 8 PTC protected Fail Safe/Fail Secure outputs. Power Supply 2: 9.5 amp @ 12VDC, 8 PTC protected Fail Safe/Fail Secure outputs. MAXIM77D Power Supply 1: 9.7 amp @ 24VDC, 8 PTC protected Fail Safe/Fail Secure outputs. Power Supply 2: 9.7 amp @ 24VDC, 8 PTC protected Fail Safe/Fail Secure outputs. |